Power unit for rail mounting, rail mounting device, 1 rail units
1208 REG
Intended use
Product characteristics
Automatic switching of light
The pulse insert is combined with a motion detector cover. As soon as the brightness drops below a value set on the motion detector cover and motions are detected, the pulse insert sends a switch-on signal cyclically to the power unit. The latter switches on the light for the set run-on time. After the run-on time has elapsed, the power unit switches the light off. After switch-off, pulse inserts with motion detector covers will not detect any motions for approx. 3 seconds.
- Manual or automatic switching of light in staircases
- Mounting on DIN rail according to EN 60715 in distribution box
- Switch-on via pulse insert or push-button
Product characteristics
- Run-on time adjustable
- Electronic overload protection for the control input
- Automatic function without switch-off warning
- Automatic function with switch-off warning
- Light switched ON continuously
- Light switched OFF continuously
Automatic switching of light
The pulse insert is combined with a motion detector cover. As soon as the brightness drops below a value set on the motion detector cover and motions are detected, the pulse insert sends a switch-on signal cyclically to the power unit. The latter switches on the light for the set run-on time. After the run-on time has elapsed, the power unit switches the light off. After switch-off, pulse inserts with motion detector covers will not detect any motions for approx. 3 seconds.
Read less...
Read more...
Information
| Article number: | 1208 REG |
|---|---|
| EAN/GTIN: | 4011377013827 |
| Installation depth: | mm |
Read less...
Read more...
Technical data
| Rated voltage: | AC 230 V ~ |
| Mains frequency: | 50 Hz |
| Power consumption: | approx. 1 W |
| Ambient temperature: | +5 ... +45 °C |
| Run-on time: | approx. 10 s ... 15 min |
| Run-on time tolerance: | ± 20 % |
| Permissible current for control input A1: | max. 40 mA |
| Switching voltage: | AC 250 V ~ |
| Switching current | |
| Ohmic: | 16 A |
| Switch-on current 20 ms: | max. 165 A |
| Connected load | |
| Incandescent lamps: | 2300 W |
| HV halogen lamps: | 2300 W |
| HV LED lamps: | 400 W |
| Fluorescent lamps parallel compensated: | 920 W |
| Fluorescent lamps non-compensated: | 1200 VA |
| Fluorescent lamps lead-lag circuit: | 2300 W / 140 µF |
| Electronic transformers: | 1500 W |
| Inductive transformers: | 1000 VA |
| Electronic ballast: | depending on type |
| Mounting width: | 18 mm (1 rail unit) |
| Total length power cable: | max. 100 m |
| Total length of control cable: | max. 100 m |
| Connection | screw terminals |
| single wire: | 1 x 0.75 ... 4.0 mm² 2 x 0.75 ... 2.5 mm² |
| stranded without ferrule: | 1 x 0.75 ... 4.0 mm² 2 x 0.75 ... 2.5 mm² |
| stranded with ferrule: | 1 x 0.5 ... 2.5 mm² |
Read less...
Read more...
Downloads
| Operating instructions | |
|---|---|
| Tendering text | |
| EC Declaration of Conformity | |
| Product data sheet |
Read less...
Read more...
Logistic
| Single item | |
|---|---|
| Packaging unit | 1 pc. |
| Weight | 0.07 KG |
| Length | 96 MM |
| Height | 20 MM |
| Width | 65 MM |
| Carton | |
| Packaging unit | 1 pc. |
| Weight | 0.096 KG |
| Length | 95 MM |
| Height | 20 MM |
| Width | 65 MM |
Read less...
Read more...