0

eNet radio switch/push-button actuator 2-gang mini

FM AS 26 UP

eNet radio switch/push-button actuator 2-gang mini
FM AS 26 UP
BPIK_Logo_eNet
BPIK_Elektrogeraete_Ruecknahme
arrow-left-slim
arrow-right-slim
  • eNet radio switch/push-button actuator 2-gang mini
Intended use
  • Switching of lighting and single-phase motors
  • Operation with suitable eNet radio transmitters
  • Installation in flush box with dimensions according to DIN 49073 in combination with a suitable cover
  • Mounting in surface-mounted housing or mounting adapter (ref.-no. FM-EBG) for false ceilings
 
Product characteristics
  • Operating mode switch for: switch/push-button actuator together for both outputs or parameterisation via eNet server
  • Independent switching of two electrical loads
  • Status feedback to radio transmitter
  • Scene operation possible
  • Status indication with LED
Switching operation:
  • Switch-on telegram: Device switches on
  • Switch-off telegram: Device switches off
 
Push-button operation:
  • Relay contact remains closed as long as ON or OFF telegrams are being received
  • The maximum switch-on time is 60 seconds
Can be set with eNet server for each output:
  • Flash function
  • Run-on time
  • Switch-on delay / switch-off delay
  • Operation as 1-way NO or 1-way NC contacts
  • Switch-off warning
  • Minimum switching repeat time
  • Operating locks
  • Continuous on, Continuous off
Supplementary functions with eNet server:
  • Fully-encrypted radio transmission (AES-CCM) from eNet server software version 2.0
  • Update of the device software
  • Repeater function
  • Reading of error memory
Read less... Read more...
BPIK_Logo_eNet
BPIK_Elektrogeraete_Ruecknahme

Information

Article number: FM AS 26 UP
EAN/GTIN: 4011377086869
Read less... Read more...

Technical data

Rated voltage:AC 230 V ~
Mains frequency:50/60 Hz
Ambient temperature:−25 ... +70 °C
Switching current at 35 °C
Ohmic:16 A (AC1)
For switching current > 10 A connecting cable 2.5 mm²
Current carrying capacity of device:Σ 16 A
Fluorescent lamps:4 AX
Contact type:µ
Stand-by power:max. 0.5 W
Connected load per output at 35 °C
Incandescent lamps:2300 W
HV halogen lamps:2000 W
Electronic transformers:1500 W
Inductive transformers:1000 VA
HV LED lamps:typical 500 W
Compact fluorescent lamps:typical 500 W
Fluorescent lamps non-compensated:920 VA
Motors:450 VA
Capacitive load:690 VA (560 µF)
Connection mode:screw terminals
single wire:1 x 0.75 ... 4 mm²
stranded with ferrule:1 x 0.75 ... 2.5 mm²
Dimensions (Ø x H):53 x 28 mm
Radio frequency:868.0 ... 868.6 MHz
Transmitting power:max. 20 mW
Transmission range in free field:typical 100 m
Receiver category:2
Read less... Read more...
Operating instructions
Operating instructions
Manual
Tendering text
EC Declaration of Conformity
Article datasheet
Read less... Read more...

Logistic

Single item
Packaging unit 1 pc.
Weight 0.07 KG
Length 82 MM
Height 45 MM
Width 82 MM
Carton
Packaging unit 10 pc.
Weight 0.807 KG
Length 235 MM
Height 92 MM
Width 175 MM
Read less... Read more...