eNet radio switch/push-button actuator 1-gang, rail mounting device, 2 rail units
FM AS 16 REG
rail mounting device, 2 rail units
Intended use
Product characteristics
Push-button operation:
Intended use
- Switching of lighting
- Operation with suitable eNet radio transmitters
- Operation with power supply (ref.-no. NT 1220 REG VDC) and eNet radio receiver (ref.-no. FM FK 32 REG) or eNet server
- Mounting on DIN rail according to EN 60715 in distribution box
Product characteristics
- Operating mode switch for: switch/push-button actuator or parameterisation via eNet server
- Status feedback to radio transmitter
- Scene operation possible
- Switchable output with Prog button
- Status indication with LED
- Switch-on telegram: Device switches on
- Switch-off telegram: Device switches off
Push-button operation:
- Relay contact remains closed as long as ON or OFF telegrams are being received
- The maximum switch-on time is 60 seconds
- Flash function
- Run-on time
- Switch-on delay / switch-off delay
- Operation as 1-way NO or 1-way NC contacts
- Switch-off warning
- Minimum switching repeat time
- Operating locks
- Continuous on, Continuous off
- Fully-encrypted radio transmission (AES-CCM) from eNet server software version 2.0
- Update of the device software
- Reading of error memory
Read less...
Read more...
Information
| Article number: | FM AS 16 REG |
|---|---|
| EAN/GTIN: | 4011377087521 |
Read less...
Read more...
Technical data
| Rated voltage: | AC 230 V ~ |
| Mains frequency: | 50/60 Hz |
| Ambient temperature: | −5 ... +45 °C |
| Switching current at AC 230 V ~ | |
| Ohmic: | 16 A |
| For switching current > 10 A connecting cable 2.5 mm² | |
| Fluorescent lamps: | 4 AX |
| Contact type: | µ |
| Stand-by power: | max. 0.2 W |
| Connected load | |
| Incandescent lamps: | 2300 W |
| HV halogen lamps: | 2000 W |
| Electronic transformers: | 1500 W |
| HV LED lamps: | typical 500 W |
| Compact fluorescent lamps: | typical 500 W |
| Inductive transformers: | 1000 VA |
| Fluorescent lamps non-compensated: | 920 VA |
| Capacitive load: | 690 VA (560 µF) |
| Connection, outputs | |
| Connection mode: | screw terminals |
| single wire: | 1 x 1.5 ... 4 mm² |
| stranded without ferrule: | 1 x 0.75 ... 4 mm² |
| stranded with ferrule: | 1 x 0.5 ... 2.5 mm² |
| Mounting width: | 36 mm (2 rail units) |
| Bus line | |
| Rated voltage: | DC 12 V SELV |
| Current consumption: | max. 20 mA |
| Connection bus: | terminal |
| Cable length: | max. 3 m |
Read less...
Read more...
Downloads
| Operating instructions | |
|---|---|
| Operating instructions | |
| Manual | |
| Tendering text | |
| EC Declaration of Conformity | |
| Article datasheet |
Read less...
Read more...
Logistic
| Single item | |
|---|---|
| Packaging unit | 1 pc. |
| Weight | 138 G |
| Length | 95 MM |
| Height | 55 MM |
| Width | 76 MM |
| Carton | |
| Packaging unit | 1 pc. |
| Weight | 138 G |
| Length | 95 MM |
| Height | 55 MM |
| Width | 76 MM |
Read less...
Read more...