KNX binary input, 6-gang, rail mounting device, 2 rail units

2116 REG

KNX binary input, 6-gang, rail mounting device, 2 rail units
2116 REG
rail mounting device, 2 rail units
6 inputs AC/DC 10 ... 230 V ~
(different line conductors possible, e.g.: E1-3 = L1 and E4-E6 = L2)
with status indicator
ETS product family: Input
Product type: Binary input

Intended use
  • Polling of conventional switching or push-button contacts, window contacts etc. in KNX systems, for reporting of states, meter levels, operation of loads, etc.
  • Mounting on DIN rail according to EN 60715 in distribution box
 
Product characteristics
  • Status LED for each input
  • Detection of voltage levels and changes on the input
  • Transmitting of input status to the bus
  • Transmitting behaviour freely adjustable
  • Functions: switching, dimming, blinds up/down, brightness values, temperatures, calling up and saving light scenes, etc.
  • Impulse and switch counter function
  • Inputs can be blocked separately
  • Connection of external AC or DC voltages
Read less... Read more...

Information about KNX binary input, 6-gang, rail mounting device, 2 rail units 2116 REG

Article number: 2116 REG
EAN/GTIN: 4011377149090
Read less... Read more...

Technical data about KNX binary input, 6-gang, rail mounting device, 2 rail units 2116 REG

KNX medium:TP 256
Rated voltage KNX:DC 21 ... 32 V SELV
Current consumption KNX:max. 7.5 mA
Connection, KNX:connection terminal
Ambient temperature:−5 ... +45 °C
Storage/transport temperature:−25 ... +75 °C
Relative humidity:max. 93 % (no condensation)
Inputs
Rated voltage:AC/DC 10 ... 230 V
Signal level "0" signal:AC/DC 0 ... 2 V
Signal level "1" signal:AC/DC 7 ... 265 V
Input current at rated voltage:
Input current:approx. 0.7 mA
Rated frequency AC signal:30 ... 60 Hz
Signal duration pulse counter:min. 100 ms
Cable length:max. 100 m
Number of contacts per input
NO contacts:max. 50
NC contacts:max. 50
Mounting width:36 mm (2 rail units)
Power loss:max. 1 W
Connection
Connection mode:screw terminals
single wire:1 x 0.5 ... 4 mm²
stranded without ferrule:1 x 0.5 ... 4 mm²
stranded with ferrule:1 x 0.5 ... 2.5 mm²
Read less... Read more...